ZCT225 Lead Wire Type Zero Phase Current Transformer phase transformation

Electrical Specification

(Customized is available)

Rated Current225A
DC Resistance at 25℃11±3Ω
Dielectric Withstanding     Voltage(Hi-pot)2500Vrms
Output Voltage Vo25-30mV
Rated Current225A
DC Resistance at 25℃11±3Ω
Dielectric Withstanding     Voltage(Hi-pot)2500Vrms
Output Voltage Vo25-30mV

The zero-sequence transformer mainly has the following applications:

  1. The outlet of the low-voltage side of the transformer of the low-voltage 400V system.
  2. Part of the feeder and motor circuit of the low-voltage 400V system.
  3. Cable outlet of medium voltage ungrounded system or small resistance grounded system.
  4. High-voltage direct grounding system transformer high-voltage neutral point bushing and neutral point grounding device.
  5. The main functions of various forms of zero-sequence transformers:
  6. The zero-sequence current transformer on the low-voltage side of the low-voltage 400V system transformer has two main functions: First, the operator detects the unbalanced current of the transformer during normal operation, which is convenient for operation adjustment. The second is to connect the zero-sequence current to the protection device of the low-voltage transformer, which is used for zero-sequence current protection on the low-voltage side of the transformer as a backup protection for the low-voltage busbar and feeder.
  7. The zero-sequence current transformers of some feeders and motor circuits of the low-voltage 400V system are mainly used to connect the zero-sequence current to the protection device for single-phase grounding zero-sequence current protection. It avoids the situation that the overcurrent protection of the loop makes the protection leapfrog action when the single-phase grounding short circuit does not meet the requirements of sensitivity.
  8. The role of the zero-sequence current transformer in the medium voltage system is mainly divided into two types: the zero-sequence current transformer of the small-current grounding system is mainly used to collect the change of the zero-sequence current of the loop when the system is single-phase grounded, and is mostly used for the grounding fault line selection device ; The secondary current access protection device of the zero-sequence current transformer of the small resistance grounding system is used for single-phase grounding current protection. Protection acts on tripping.
  9. The neutral point zero-sequence current transformer of the high-voltage direct grounding system is mainly used for the zero-sequence current protection of the high-voltage side of the transformer; the zero-sequence current transformer of the transformer neutral point grounding device is mainly used for the gap zero-sequence current protection.
ItemRated Current(A)Output Voltage
Vo(mv)
Test ConditionsOver Leakage
Characterstics
Temperature
Characteristics
-35~80℃
Dimensions
(mm)
Click PN For DetailsIDODHT
ZCT201304-5.1lin=10mA RL=510-10%~0%10%Max5.9166.5
ZCT202305.1-6lin=8mA RL=750-10%~0%10%Max5.815.26.1
ZCT2035017-21lin=22.5mA RL=1k-10%~0%10%Max9.2217.3
ZCT2043012-15lin=22.5mA RL=1k-10%~0%10%Max9.820.66.5
ZCT2053012.5-15.5lin=8mA RL=4.7k-10%~0%10%Max9.321.37.2
ZCT2065017-21lin=22.5mA RL=1k-10%~0%10%Max12.32610
ZCT207307.5-8.5lin=25mA RL=1k-10%~0%10%Max15.429.810
ZCT2086010.2-12.5lin=20mA RL=680-10%~0%10%Max7.219.47.7
ZCT209508-11.2lin=11.25mA RL=1k-10%~0%10%Max717.27
ZCT210508-11.2lin=11.25mA RL=1k-10%~0%10%Max6.816.97.9
ZCT211508-11.2lin=11.25mA RL=1k-10%~0%10%Max10.625.48
ZCT2126010.2-12.5lin=20mA RL=680-10%~0%10%Max1123.58
ZCT21360≥300lin=25mA RL=1k-10%~0%10%Max9.423.812.7
ZCT2186010.2--12.5lin=25mA RL=680-10%~0%10%Max7.518.97.6
ZCT22060≥300lin=25mA RL=47k-10%~0%10%Max10.12411.5
ZCT22560≥300lin=25mA RL=47k-10%~0%10%Max10.925.59
ZCT40110017-21lin=22.5mA RL=1k-10%~0%10%Max1529.210
ZCT4021006.3-7.5lin=20mA RL=370-10%~0%10%Max17.535.98.8
ZCT40325017-21lin=22.5mA,RL=1k-10%~0%10%Max295112
ZCT40425017-21lin=22.5mA,RL=1k-10%~0%10%Max3255.612
ZCT40525017-21lin=22.5mA,RL=1k-10%~0%10%Max4280*6920
ZCT40663017-21lin=25mA,RL=1k-10%~0%10%Max51.38426
ZCT40780017-21lin=22.5mA,RL=1k-10%~0%10%Max5196*8923
ZCT408100125-150lin=500mA,RL=150-10%~0%10%Max193611.5
ZCT409225125-150lin=500mA,RL=150-10%~0%10%Max244212
ZCT410400125-150lin=500mA,RL=150-10%~0%10%Max4390*7416
ZCT411800120-151lin=500mA,RL=150-10%~0%10%Max5396*8923